Reference

Code lookup by topic

Where to look in the code for the questions that come up on the job. Our one-line summaries point you to the section; read the code book for the full rule and its exceptions.

Receptacles and GFCI

GFCI in dwellings

210.8(A)

Bathrooms, garages and accessory buildings, outdoors, crawl spaces, basements, kitchens, laundry areas, within 6 ft of sinks, tubs and showers, and boathouses.

Receptacles and GFCI

GFCI in commercial and other buildings

210.8(B)

Bathrooms, kitchens, rooftops, outdoors, near sinks, indoor wet locations, locker rooms, garages and service bays, and more.

Receptacles and GFCI

GFCI for outdoor equipment outlets

210.8(F)

Outdoor outlets at dwellings, including hardwired HVAC equipment, need GFCI protection (with listed exceptions).

Receptacles and GFCI

AFCI protection

210.12

Most 120 V, 15 and 20 A dwelling circuits feeding outlets in living areas, kitchens and laundry areas. Also for extensions and replacements.

Receptacles and GFCI

Tamper-resistant receptacles

406.12

15 and 20 A, 125 and 250 V receptacles in dwellings and many other occupancies (schools, hotels, waiting areas) must be tamper-resistant.

Receptacles and GFCI

Wet and damp location receptacles

406.9

Weather-resistant receptacles outdoors; in wet locations, an in-use (extra-duty) cover that stays weatherproof with a cord plugged in.

Receptacles and GFCI

Replacing receptacles

406.4(D)

Where no ground is available, the options: a non-grounding receptacle, a GFCI, or a grounding receptacle fed from a GFCI and marked.

Branch circuits

Kitchen countertop circuits

210.11(C)(1)210.52(B)

At least two 20 A small-appliance circuits for kitchen, dining and pantry receptacles.

Branch circuits

Countertop receptacle spacing

210.52(C)

No point along the counter wall line more than 24 in from a receptacle; any counter space 12 in or wider gets one.

Branch circuits

Wall receptacle spacing

210.52(A)

No point along the floor line more than 6 ft from a receptacle; any wall 2 ft or wider counts.

Branch circuits

Bathroom circuits and receptacles

210.11(C)(3)210.52(D)

A 20 A circuit for bathroom receptacles, and a receptacle within 3 ft of each basin.

Branch circuits

Laundry circuit

210.11(C)(2)210.52(F)

At least one 20 A circuit for laundry receptacles, with no other outlets on it.

Branch circuits

Outdoor and balcony receptacles

210.52(E)

Dwellings need receptacles at the front and back, and on balconies, decks and porches that are reachable from inside.

Branch circuits

Service receptacle at HVAC equipment

210.63

A 125 V receptacle within 25 ft of heating, AC and refrigeration equipment, on the same level.

Branch circuits

Continuous loads (125%)

210.19(A)(1)210.20(A)215.2(A)(1)

A load running 3 hours or more: size the conductors and the breaker at 125% of it.

Branch circuits

Small conductor protection

240.4(D)

14 AWG copper on 15 A, 12 AWG on 20 A, 10 AWG on 30 A, unless a specific article allows otherwise (motors, AC equipment).

Wire size calculator →

Branch circuits

Multiwire branch circuits

210.4

Shared-neutral circuits need a common disconnect (handle ties or a multi-pole breaker), and the neutral pigtailed, not run through device screws.

Branch circuits

Voltage drop

210.19 Informational Note215.2 Informational Note

Advisory, not required: 3% on a branch circuit or feeder, 5% total.

Voltage drop calculator →

Branch circuits

Dwelling load calculation

220.40 onward220.82

The standard method (Part III) or the optional method for one dwelling unit (220.82).

Dwelling load calculator →

Wiring methods

Conductor ampacity and derating

310.16310.15(B)310.15(C)(1)

Table 310.16 values, corrected for ambient temperature and adjusted for more than three current-carrying conductors.

Wire size calculator →

Wiring methods

Terminal temperature limits

110.14(C)

Use the 60 °C column for 100 A and less (or 14–1 AWG) and 75 °C above, unless the equipment is marked otherwise.

Wiring methods

Torque on terminals

110.14(D)

Where the maker gives a torque value, tighten to it with a calibrated tool.

Wiring methods

NM cable support

334.30

Secure within 12 in of boxes and at least every 4½ ft.

Wiring methods

EMT support

358.30

Secure within 3 ft of each box or fitting and at least every 10 ft.

Wiring methods

PVC support and expansion

352.30352.44

Support spacing grows with the trade size; use expansion fittings where temperature change moves the run ¼ in or more.

Wiring methods

Bends between pull points

358.26344.26352.26

No more than 360° of bends between pull points.

Bending calculator →

Wiring methods

Conduit fill

Chapter 9 Table 1Annex C

53% for one conductor, 31% for two, 40% for three or more.

Conduit fill calculator →

Wiring methods

Burial depth

300.5Table 300.5

Minimum cover depends on the wiring method and the location: commonly 24 in for direct-burial cable, 18 in for PVC and 6 in for rigid.

Wiring methods

Underground raceways are wet

300.5(B)310.10(C)

The inside of an underground raceway is a wet location: use wet-rated conductors (THWN-2, XHHW-2).

Wiring methods

Fire-rated penetrations

300.21

Restore the fire rating of walls, floors and ceilings you penetrate, using listed methods.

Wiring methods

Cables in attics

334.23320.23

Cables across joists in accessible attics need protection within 6 ft of the scuttle, or wherever there are permanent stairs or ladders.

Boxes and devices

Box fill

314.16

Count conductors, clamps, devices and grounds, and make sure the box volume covers them.

Box fill calculator →

Boxes and devices

Ceiling fan and fixture boxes

314.27(C)314.27(A)

Fans hang only from boxes listed for fan support. Boxes in a ceiling at a fixture location must support at least 50 lb.

Boxes and devices

Neutral at switch locations

404.2(C)

Most switch locations need a neutral, so electronic controls can be added later.

Wiring diagrams →

Boxes and devices

Switch and breaker height

404.8(A)240.24(A)

The handle at its highest position no more than 6 ft 7 in above the floor or platform.

Boxes and devices

Boxes in wet and damp locations

314.15

Keep water out of boxes and fittings; listed for wet locations where they are.

Lighting

Required lighting outlets

210.70

A switched light in every habitable room, bathroom, hallway, stairway, garage and at outdoor entrances; stairs over 6 risers need switches at each level.

Lighting

Luminaires in clothes closets

410.16

Enclosed or LED fixtures only, with set clearances from the storage space.

Lighting

Recessed lights in insulation

410.116

Use IC-rated fixtures where insulation will touch them; otherwise keep the listed clearances.

Lighting

Lights over tubs and showers

410.10(D)

Within 3 ft horizontally and 8 ft above the tub rim, fixtures must be listed for damp (or wet, if subject to spray) locations.

Services and panels

Working space at panels

110.26(A)

Commonly 36 in deep (more at higher voltages), 30 in wide or the equipment width, and 6½ ft high, kept clear.

Services and panels

Where panels can’t go

240.24(D)240.24(E)240.24(F)

No overcurrent devices in bathrooms (dwellings), clothes closets or over stair steps.

Services and panels

Service disconnect location and number

230.70230.71

At a readily accessible place nearest where the service conductors enter; limits on how many disconnects.

Services and panels

Outdoor emergency disconnect (dwellings)

230.85

One- and two-family dwellings need a readily accessible emergency disconnect outside.

Services and panels

Surge protection at dwelling services

230.67

Services to dwelling units need a Type 1 or Type 2 surge-protective device.

Services and panels

Overhead service clearances

230.24230.26

Minimum heights above roofs, yards, driveways and streets for overhead service conductors.

Services and panels

Available fault current and arc flash labels

110.24110.16

Mark available fault current on service equipment; field-mark arc flash warnings on equipment likely to be worked on energized.

Grounding

EGC size

Table 250.122

Sized from the breaker or fuse ahead of the circuit.

Grounding lookup →

Grounding

Grounding electrode system

250.50250.52250.53

Bond together every electrode present; rods need 25 Ω or a second rod at least 6 ft away.

Grounding

Neutral-to-ground bond at the service only

250.24(A)(5)250.142(B)

After the service disconnect, keep neutrals and grounds apart; remove the bonding screw in subpanels.

Grounding

Feeders to separate buildings

250.32

Run an EGC with the feeder, keep the neutral isolated, and add a grounding electrode at the building.

Grounding

Transformers (separately derived systems)

250.30

Bond the neutral to ground at one point and run a GEC from there.

Transformers →

Equipment

Motor branch circuits

430.6430.22430.32430.52

Conductors at 125% of table FLC, overloads from the nameplate, short-circuit protection from Table 430.52.

Motor calculator →

Equipment

Motor disconnect in sight

430.102

A disconnect in sight of the controller and the motor (in sight means visible and within 50 ft), or a lockable one with conditions.

Equipment

AC equipment disconnect and sizing

440.14440.22440.32

Disconnect within sight of the unit; conductors and breaker from the nameplate MCA and maximum OCPD.

Equipment

Transformer protection

450.3(B)

Primary only, or primary and secondary, with percent limits.

Transformers →

Equipment

EV chargers

625.40625.42625.54

Individual branch circuit, sized at 125% of the charger rating as a continuous load; GFCI for receptacles.

Equipment

Solar PV

690705.12690.12

Article 690 for the PV system, 705.12 for connecting at a panel (the 120% rule), 690.12 for rapid shutdown.

Equipment

Standby generators and transfer switches

702445702.5

Optional standby systems need transfer equipment so the generator can’t backfeed the utility.

Special

Pools and hot tubs

680.21680.22680.26

GFCI for pumps and receptacles, receptacle distances, and the equipotential bonding grid.

Special

Temporary power

590.4590.6

Construction power: GFCI for personnel on receptacles, and how long temporary wiring can stay.

Special

Hazardous locations

500–516

Classified locations: Class/Division or Zone. Fuel dispensing is 514; spray booths 516.

2023 NEC numbering. Your jurisdiction may be on a different edition or have local amendments: check with the AHJ.