Reference

Transformers

Full-load current, the biggest breaker or fuse allowed, and how the common connections work. For transformers 1000 V and less.

Current and protection

Phase
kVA
V
V

Protection planSideMax %Max rating

Max rating is the largest standard fuse or breaker allowed. At 9 A and up, 125% may round up to the next standard size; the other limits can't be exceeded. Secondary conductors also need protection under 240.21(C) (tap rules) — size them from the secondary current.

NEC: 450.3(B), Table 450.3(B) Note 1, 240.6(A), 240.21(C)

Full-load current formulas

Single-phase: I = kVA × 1000 ÷ V

Three-phase: I = kVA × 1000 ÷ (V × 1.732)

Common 480 to 208Y/120 V three-phase sizes

kVAPrimary A (480 V)Secondary A (208 V)
1518.041.6
3036.183.3
4554.1124.9
7590.2208.2
112.5135.3312.3
150180.4416.4
225270.6624.5

Connections

Delta-wye (480 V delta to 208Y/120 V)

Single-phase 120/240 V

Buck-boost

Checks before you energize

NEC: 250.30, 450.4, 450.9, 450.14 (disconnecting means)