The steps that keep you alive: de-energize, lock it, prove it dead. This is a refresher, not training. Follow your employer's written program and NFPA 70E.

Lockout/tagout: the electrically safe work condition

  1. Find every source of supply, from up-to-date drawings, labels and a walk-down. Watch for backfeeds: generators, PV, UPS, control power from another panel, capacitors.
  2. Shut off the load, then open the disconnecting device for each source.
  3. Where you can, look at the blades or the racked-out breaker to see it's open.
  4. Put your own lock and tag on each disconnect. Only you remove your lock.
  5. Test each phase conductor or circuit part, phase to phase and phase to ground, with a properly rated tester, checking the tester on a known source before and after.
  6. Where there could be induced voltage or stored energy, ground the conductors with rated temporary grounds before touching them.

Until the test is done, treat it as energized and wear the PPE for live work.

Live-dead-live

  1. Live: check your meter on a known live source (or a proving unit) on the voltage range you'll use.
  2. Dead: test the de-energized circuit: every phase to every phase, and each phase to ground.
  3. Live: check the meter again on the known source. If it failed between steps, your "dead" reading means nothing.

Shock approach boundaries (AC, 50 to 750 V)

Voltage, phase to phaseLimited: movable conductorLimited: fixed partRestricted
50 to 150 V10 ft 0 in3 ft 6 inAvoid contact
151 to 750 V10 ft 0 in3 ft 6 in1 ft 0 in

Arc flash basics

PPE categories

CategoryMinimum arc ratingTypical gear
14 cal/cm²Arc-rated shirt and pants or coverall, face shield or arc flash suit hood, hard hat, safety glasses, hearing protection, leather gloves or rubber gloves with protectors
28 cal/cm²As category 1, with an arc-rated balaclava under the face shield (or a hood), and leather work shoes
325 cal/cm²Arc flash suit: jacket, pants, hood and gloves
440 cal/cm²Heavier arc flash suit, same pieces

Rubber insulating gloves

ClassMax use voltage (AC)
00500 V
01,000 V
17,500 V
217,000 V
326,500 V
436,000 V

NFPA 70E (Article 120, 130.4, Table 130.5(G), Table 130.7(C)(15)(c)); OSHA 1910.147, 1910.333, 1926.417