Voltage too high or too low
Measured voltage outside the normal range, or sagging under load. Service, feeder, branch circuit or a system mismatch.
Before you start
How much electrical experience do you have?
This sets how much detail each step shows. You can change it any time.
Showing detail
How it works
Utilities aim to deliver voltage within ANSI C84.1 Range A at the service: plus or minus 5% of nominal, which is 114 to 126 V on a 120 V system and 228 to 252 V on 240 V. Range B is a wider band allowed less often. Voltage that is high or low everywhere, at light load, is a utility issue they fix with transformer taps or regulators. Voltage that sags only under load comes from resistance: in the utility transformer and drop, the service conductors, the feeder or the branch circuit. Equipment rated 230 V running on a 208 V system is a different problem: the system is fine, the equipment doesn’t match it.
Every question and answer in this guide. Tap “Step by step” to walk through it.
- Where is the voltage wrong?
- Everywhere in the buildingTest: Record the service voltageExpect: Within ANSI Range A: 114 to 126 V to neutral on a 120 V system at all times, legs within a few volts of each other.
- Above 126 V, highest at light loadUtility voltage running high
- Below 114 V even at light loadUtility voltage running low
- Normal at light load, sags a lot under loadTest: Find where the drop happensExpect: A few volts of drop at full load. NEC informational notes suggest about 3% on a branch circuit or feeder and 5% total, as a design guide.
- Most of the drop is at the mainResistance between the transformer and the main
- Main holds, the load end sagsToo much drop in the feeder or branch circuit
- Legs unequal and shifting with loadA loose or open neutral
- One circuit or one areaTest: Measure drop on the circuit under loadExpect: A drop of a few volts at most, and hot to neutral about equal to hot to ground.
- Drops more than about 5% (6 V)Too much drop in the feeder or branch circuit
- Holds steadyThe circuit holds voltage
- Equipment says 230 or 240 V; the building is 208Y/120 VEquipment rated for 240 V on a 208 V system
- Everywhere in the buildingTest: Record the service voltageExpect: Within ANSI Range A: 114 to 126 V to neutral on a 120 V system at all times, legs within a few volts of each other.