VFD overcurrent fault
When the fault happens tells you whether it’s the ramp, the load, or a short on the drive output.
Before you start
How much electrical experience do you have?
This sets how much detail each step shows. You can change it any time.
Showing detail
How it works
A VFD turns incoming AC into DC on an internal bus, then switches that DC with transistors (IGBTs) to build a variable-frequency output for the motor. The transistors can only survive a limited current for a very short time, so the drive watches output current closely and trips fast. An overcurrent fault means the motor current spiked past the drive’s limit: the drive asked for too much too fast, the load jammed, or there’s a short or ground on the output.
Every question and answer in this guide. Tap “Step by step” to walk through it.
- When does the overcurrent fault happen?
- The instant it gets a run commandTest: Insulation-test the motor and leads, with the drive disconnectedExpect: Insulation well above 5 MΩ to ground, and three equal lead-to-lead resistances.
- Low to ground or lead to leadShort or ground fault in the motor or output leads
- Motor and leads test goodPossible failed drive output section
- While speeding upHow is the acceleration time and boost set, compared with the load?
- Short ramp or high-inertia loadAccel ramp too fast for the load
- Motor data not entered or doesn’t matchMotor data not set in the drive
- Settings look reasonableTest: Compare running current to the motor and drive ratingsExpect: At or below motor FLA, balanced between the three leads, and within the drive’s output rating.
- Near or above the drive’s ratingDrive too small for the motor or duty
- Spikes when the machine binds or loads upMechanical overload or jam
- Unbalanced between leadsTest: Insulation-test the motor and leads, with the drive disconnectedExpect: Insulation well above 5 MΩ to ground, and three equal lead-to-lead resistances.
- Low to ground or lead to leadShort or ground fault in the motor or output leads
- Motor and leads test goodPossible failed drive output section
- While running at speedTest: Compare running current to the motor and drive ratingsExpect: At or below motor FLA, balanced between the three leads, and within the drive’s output rating.
- Near or above the drive’s ratingDrive too small for the motor or duty
- Spikes when the machine binds or loads upMechanical overload or jam
- Unbalanced between leadsTest: Insulation-test the motor and leads, with the drive disconnectedExpect: Insulation well above 5 MΩ to ground, and three equal lead-to-lead resistances.
- Low to ground or lead to leadShort or ground fault in the motor or output leads
- Motor and leads test goodPossible failed drive output section
- When a contactor or disconnect on the output opens or closesSwitching between the drive and the motor while running
- The instant it gets a run commandTest: Insulation-test the motor and leads, with the drive disconnectedExpect: Insulation well above 5 MΩ to ground, and three equal lead-to-lead resistances.