Old 2-prong outlets: safe upgrade options
Add a real ground, use GFCI protection with labels, or replace with a 2-prong. Never a bootleg ground.
Before you start
How much electrical experience do you have?
This sets how much detail each step shows. You can change it any time.
Showing detail
How it works
Two-prong receptacles come from wiring with no equipment grounding conductor, so there’s no low-resistance path to carry fault current and trip the breaker if a metal case becomes energized. You can’t create a ground by jumpering neutral to the ground screw. When a 2-prong receptacle is replaced, the code allows a few paths: connect to a real grounding conductor, use GFCI protection with the right labels, or install another non-grounding receptacle.
Every question and answer in this guide. Tap “Step by step” to walk through it.
- With the breaker off, pull the receptacle out. What wiring do you see?
- Metal box with metal conduit or armored cableTest: Measure hot to the metal boxExpect: About 120 V if the box has a ground path.
- About 120 VTest: Confirm a solid ground pathExpect: A low, steady reading, a few ohms or less.
- Low and steadyThe box is grounded through the raceway
- High, open or jumps aroundCan a grounding conductor be run to this box?
- YesAdd a grounding conductor
- No, not practicalWhich option fits?
- A GFCI receptacle at this spotUse a GFCI receptacle without a ground
- A GFCI breaker or first receptacle protecting the runGFCI protection for the whole run
- Put back a 2-prong receptacleReplace with a non-grounding receptacle
- 0 V or a few voltsCan a grounding conductor be run to this box?
- YesAdd a grounding conductor
- No, not practicalWhich option fits?
- A GFCI receptacle at this spotUse a GFCI receptacle without a ground
- A GFCI breaker or first receptacle protecting the runGFCI protection for the whole run
- Put back a 2-prong receptacleReplace with a non-grounding receptacle
- About 120 VTest: Confirm a solid ground pathExpect: A low, steady reading, a few ohms or less.
- Two-wire cable, no ground wireCan a grounding conductor be run to this box?
- YesAdd a grounding conductor
- No, not practicalWhich option fits?
- A GFCI receptacle at this spotUse a GFCI receptacle without a ground
- A GFCI breaker or first receptacle protecting the runGFCI protection for the whole run
- Put back a 2-prong receptacleReplace with a non-grounding receptacle
- Single wires on porcelain knobs or tubesKnob and tube wiring
- Metal box with metal conduit or armored cableTest: Measure hot to the metal boxExpect: About 120 V if the box has a ground path.