Primary trips when the transformer is energized

Inrush, faults, secondary loads and protection settings when the primary breaker won’t hold.

Before you start

How much electrical experience do you have?

This sets how much detail each step shows. You can change it any time.

How it works

When a transformer is switched on, its core can draw a magnetizing inrush current of roughly 8 to 12 times rated current for a few cycles, depending on its size, design and where in the AC cycle the switch closes. Magnetism left in the core from the last shutdown can make it worse, which is why it may trip only sometimes. The primary breaker has to ride through that inrush while still protecting the transformer within the limits of 450.3(B).