Wireman · Changing taps for high or low voltage: troubleshooting for electricians · 2023 NEC ·
Changing taps for high or low voltage
Work out how far off you are, pick the right tap and change it safely.
Before you start
How much electrical experience do you have?
This sets how much detail each step shows. You can change it any time.
Showing detail
How it works
Most general-purpose dry-type transformers have taps on the primary winding, commonly in 2.5% steps (for example, two above and four below nominal). Connecting to a tap with more primary turns lowers the secondary voltage; fewer turns raises it. These are no-load taps: the transformer must be de-energized to change them, and every coil must be set to the same tap.
Every question and answer in this guide. Tap “Step by step” to walk through it.
- Test: Measure the primary and secondaryExpect: Secondary within about 2.5% of nominal (one tap step).
- Secondary highIs the primary also high by about the same percent?
- Yes, primary is highRetap for high supply voltage
- No, primary is normalTap is set wrong
- Secondary lowIs the secondary low at light load, or only under heavy load?
- Low even at light load, primary also lowRetap for low supply voltage
- Low at light load, primary normalTap is set wrong
- Only low under heavy loadVoltage drop under load
- Within about 2.5%No tap change needed
- Secondary highIs the primary also high by about the same percent?