Wireman · Test a breaker: troubleshooting for electricians · 2023 NEC ·
Test a breaker
What you can really check in the field, and when a breaker needs proper trip testing.
Before you start
How much electrical experience do you have?
This sets how much detail each step shows. You can change it any time.
Showing detail
How it works
A thermal-magnetic breaker has a bimetal that bends with heat to trip on overload and a magnetic coil that trips instantly on a short. You can’t check those trip points with a multimeter. In the field you can check the breaker’s condition: how it looks, how hot it runs, whether it’s tight, and how much voltage it drops when closed and carrying load. Proving it trips at the right current takes primary-injection test equipment.
Every question and answer in this guide. Tap “Step by step” to walk through it.
- Why are you testing the breaker?
- It trips and I suspect the breakerTest: Measure the load on itExpect: Below the breaker rating, and below 80% of it for loads that run for hours.
- At or above its ratingThe breaker is protecting an overloaded circuit
- Well below its ratingTest: Look and check temperature
- Discolored, cracked, buzzing or much hotter than neighborsOverheated or damaged breaker
- Looks and runs normalTest: Measure voltage drop across the closed breakerExpect: A small fraction of a volt, similar to an identical breaker at similar load.
- Low and similar to its neighborsTest: Check the connections dead
- Loose, pitted or discoloredLoose or burned connection
- Tight and cleanPasses every field check
- Several times higher, or near a volt or moreHigh resistance in the breaker or its connection
- Low and similar to its neighborsTest: Check the connections dead
- It’s hot, buzzing or smellsTest: Look and check temperature
- Discolored, cracked, buzzing or much hotter than neighborsOverheated or damaged breaker
- Looks and runs normalTest: Measure voltage drop across the closed breakerExpect: A small fraction of a volt, similar to an identical breaker at similar load.
- Low and similar to its neighborsTest: Check the connections dead
- Loose, pitted or discoloredLoose or burned connection
- Tight and cleanPasses every field check
- Several times higher, or near a volt or moreHigh resistance in the breaker or its connection
- Low and similar to its neighborsTest: Check the connections dead
- It won’t reset or stay onReset problem: follow the reset guide
- Maintenance: will it trip correctly?Trip testing needs primary injection
- It trips and I suspect the breakerTest: Measure the load on itExpect: Below the breaker rating, and below 80% of it for loads that run for hours.