How it works
A PLC input card watches for voltage across each input and its common. Most DC inputs are 24 V DC. A sinking input expects the field device to supply +24 V to it (so it pairs with a sourcing or PNP sensor), and a sourcing input expects the field device to pull it to 0 V (so it pairs with a sinking or NPN sensor). Either way, the input LED shows what the card sees, and the program decides what to do with it. That gives three places to check: the field wiring, the card, and the logic.
Every question and answer in this guide. Tap “Step by step” to walk through it.
- When the device should be on, is that input’s LED lit on the card?
- LED on, program doesn’t reactOnline with the PLC, does the input’s bit change state in the program?
- Bit doesn’t change, or it’s forcedAddress mismatch, force, or PLC not in Run
- Bit changes, but the output doesn’t followThe program logic is holding things up
- LED offTest: Measure across the input and its commonExpect: About 24 V DC across the input when the device is on, near 0 V when it’s off. The supply reads about 24 V DC. Check the card’s on and off thresholds in its spec.
- No 24 V supplyNo 24 V DC supply
- Never changes when device operatesField device or wiring
- 24 V across the input, LED still offIs the card’s common wired to the correct side of the supply for this card and sensor type?
- Mismatched or common not landedSinking/sourcing mismatch or missing common
- Wiring matches the cardFailed input point or card
- LED stays on all the timeTest: Measure the input with the device offExpect: Near 0 V with the device off, and the LED out.
- Voltage present with device offLeakage or a stuck field device
- LED stays on with the wire liftedFailed input point or card
- LED on, program doesn’t reactOnline with the PLC, does the input’s bit change state in the program?