Burn marks, melted bus or scorched breaker
Figure out what burned (wire, breaker, bus or service lugs) and what has to be replaced.
Before you start
How much electrical experience do you have?
This sets how much detail each step shows. You can change it any time.
Showing detail
How it works
Breakers clip onto bus stabs, which are fingers of the bus bar. When a connection there or at a wire terminal loosens, its resistance heats the metal, the plating oxidizes, and the heat feeds itself until it arcs. Damage on the bus means a new breaker won’t make good contact either, so the repair depends on what burned: the wire, the breaker, the bus or the service lugs.
Every question and answer in this guide. Tap “Step by step” to walk through it.
- Is anything smoking, sizzling or hot right now?
- YesActive overheating or fire
- No, it’s old damageTest: Find what burned
- Wire insulation at a breaker terminalWhat is the wire at that terminal?
- Aluminum (dull silver)An aluminum wire connection failed
- Smaller than the breaker allowsThe breaker is too big for the wire
- Copper, the right sizeA loose wire connection
- Breaker melted, stab under it is cleanA failed breaker, bus still good
- Bus stab pitted, burned or meltedBus damage
- Main lugs or service conductorsBurned service connections
- Rust, water stains or tracking marksWater in the panel
- Wire insulation at a breaker terminalWhat is the wire at that terminal?