Motor trips the breaker on start

Faults, jammed loads, long starts and breakers that are too small or set too low.

Before you start

How much electrical experience do you have?

This sets how much detail each step shows. You can change it any time.

How it works

A starting motor draws locked-rotor current, commonly around 6 times its full-load amps, until it picks up speed, plus a brief extra spike in the first half cycle. The motor branch breaker or fuse is sized well above full-load current, using the NEC table current and Table 430.52, so it rides through the start, while the overload relay handles running overloads. A breaker that trips on start means a fault, a start that takes too long, too much current, or a protective device too small or set too low.