Wireman · Motor runs slow or won’t reach speed: troubleshooting for electricians · 2023 NEC ·
Motor runs slow or won’t reach speed
Low voltage, a lost phase, a wrong connection, overload or a weak capacitor.
Before you start
How much electrical experience do you have?
This sets how much detail each step shows. You can change it any time.
Showing detail
How it works
An induction motor runs a little below its synchronous speed, which is set by its poles and the line frequency: 3600, 1800, 1200 or 900 rpm at 60 Hz. The difference, called slip, grows with load, so an 1800 rpm motor’s nameplate might say 1750. A motor that won’t come up to speed is short on torque (low voltage, a lost phase, a wrong connection, a weak capacitor) or is carrying more load than it can handle.
Every question and answer in this guide. Tap “Step by step” to walk through it.
- When is it slow?
- Takes a long time to come up, or never doesTest: Measure voltage at the motorExpect: Within 10% of nameplate, and balanced between phases.
- Low, more than 10% under nameplateLow voltage at the motor
- One phase missing or very lowSingle-phasing
- NormalIs it a dual-voltage motor? Compare the connection to the nameplate diagram.
- Connected for the wrong voltageMotor connected for the wrong voltage
- Connected correctly, or single voltageIs it a single-phase motor?
- Yes, single phaseWeak capacitor or start switch
- No, three phasePossible rotor problem
- Comes up, then slows under loadTest: Measure current under loadExpect: At or below FLA.
- Above FLAToo much load
- At or below FLABelt or coupling slip
- It’s on a VFDDrive settings or speed reference
- Takes a long time to come up, or never doesTest: Measure voltage at the motorExpect: Within 10% of nameplate, and balanced between phases.