Ground-fault alarm on an ungrounded or HRG system

Read the ground detector lamps, confirm the faulted phase and find the feeder before a second fault.

Before you start

How much electrical experience do you have?

This sets how much detail each step shows. You can change it any time.

How it works

On an ungrounded system no conductor is tied to earth, so the first phase-to-ground fault doesn’t trip anything: that phase just drops to ground potential and the other two rise to full line-to-line voltage to ground. A high-resistance grounded (HRG) wye works the same way but uses a resistor from neutral to ground to limit fault current to a few amps and hold voltages steady. Both keep running through a first fault, so the code requires ground detection, and the fault must be found before a second fault on another phase becomes a phase-to-phase short through the ground.