Emergency or exit light fails its test

Unit won’t light on the test button, dies before 90 minutes, shows no charge, or stays on with power on.

Before you start

How much electrical experience do you have?

This sets how much detail each step shows. You can change it any time.

How it works

Unit equipment has a battery, a charger and a transfer circuit that watches its normal supply. When normal power drops, it switches the lamps to the battery. Life-safety rules (NFPA 101, adopted by the local fire code) generally call for a 30-second functional test every month and a 90-minute test once a year, with written records. The unit should be fed from the same branch circuit as the normal lighting in its area, ahead of any local switch, so it sees the same outage the lights do. Batteries wear out with age and heat and are the most common failure.