Wireman · Receptacle or circuit is dead: troubleshooting for electricians · 2023 NEC ·
Receptacle or circuit is dead
No power at an outlet or a group of outlets. Work through it from the panel to the box.
Before you start
How much electrical experience do you have?
This sets how much detail each step shows. You can change it any time.
Showing detail
How it works
Receptacles are usually wired in a chain. Power goes to the first one, then on to the next through its screws or push-in (back-stab) holes. When one connection loosens, everything after it goes dead. Many dead receptacles are actually downstream of a tripped GFCI in another room.
Every question and answer in this guide. Tap “Step by step” to walk through it.
- Check the panel. Is any breaker tripped?
- Yes, and it held when I reset itA tripped breaker
- Yes, and it trips againThe breaker won’t hold
- No tripped breakersPress TEST, then RESET, on every GFCI receptacle nearby. Did power come back?
- Yes, it’s backA tripped GFCI upstream
- A GFCI won’t resetA GFCI that won’t reset
- No changeIs the receptacle controlled by a wall switch?
- Yes, it works with the switch onA switched receptacle
- No, still deadTest: Measure at the receptacleExpect: About 120 V on both.
- 0 V on bothTest: Find the last working receptacle
- A loose, back-stabbed or burned connectionA failed connection at a receptacle upstream
- Everything looks tightA break in a hidden splice or the cable itself
- Hot–neutral 0 V, hot–ground 120 VOpen neutral on the branch circuit
- 120 V on bothThe receptacle has power; the problem is the contact or what’s plugged in
- Hot–neutral 120 V, hot–ground 0 VOpen ground (the receptacle works but isn’t grounded)
- 0 V on bothTest: Find the last working receptacle