Wireman · 4–20 mA sensor reading wrong: troubleshooting for electricians · 2023 NEC ·
4–20 mA sensor reading wrong
Measure the loop current, then decide whether it’s the transmitter, the loop or the scaling.
Before you start
How much electrical experience do you have?
This sets how much detail each step shows. You can change it any time.
Showing detail
How it works
A 4–20 mA loop sends a measurement as a current: 4 mA is 0% of the range and 20 mA is 100%, so 12 mA is 50%. Current is the same everywhere in a series loop, so wire resistance doesn’t change the reading. Starting at 4 mA instead of 0 lets the system tell a real zero from a broken wire: 0 mA usually means the loop is open. Many PLC inputs read the current through a 250 Ω resistor, which turns 4–20 mA into 1–5 V.
Every question and answer in this guide. Tap “Step by step” to walk through it.
- What is the display or PLC showing?
- Zero, below range, or a faultTest: Check the loop supply at the transmitterExpect: The loop supply (commonly 24 V DC) at the source, and at the transmitter at least the minimum voltage in its manual.
- No voltage at the supplyNo loop power
- Supply good, 0 V at the transmitterOpen loop
- Full supply voltage at the transmitterThe transmitter isn’t drawing loop current
- Voltage present, but below the minimumNot enough voltage for the transmitter
- Pegged at maximumTest: Measure the loop current in seriesExpect: A steady current between 4 and 20 mA that matches the process (for example 12 mA at half range).
- Correct current, display wrongScaling or configuration error
- Current wrong for the processTransmitter calibration or sensing problem
- Above 20 mA or below 4 mAOut-of-range current: a fault or a short
- Current is noisy or jumpsElectrical noise or a grounding problem
- Reads, but wrong or jumpyTest: Measure the loop current in seriesExpect: A steady current between 4 and 20 mA that matches the process (for example 12 mA at half range).
- Correct current, display wrongScaling or configuration error
- Current wrong for the processTransmitter calibration or sensing problem
- Above 20 mA or below 4 mAOut-of-range current: a fault or a short
- Current is noisy or jumpsElectrical noise or a grounding problem
- Zero, below range, or a faultTest: Check the loop supply at the transmitterExpect: The loop supply (commonly 24 V DC) at the source, and at the transmitter at least the minimum voltage in its manual.