A/C outdoor unit won’t run

Split it at the contactor: is the 24 V call arriving, and is 240 V getting through?

Before you start

How much electrical experience do you have?

This sets how much detail each step shows. You can change it any time.

How it works

When the thermostat calls for cooling, it connects R to Y. That 24 V signal travels from the furnace or air handler out to the condenser and energizes the contactor coil, which closes and sends 240 V to the compressor and fan. The indoor blower runs separately on G. So the outdoor unit needs two things at once: line voltage from its own breaker and disconnect, and the 24 V call from the indoor unit’s transformer.